Permit Number: T16CM09367
Parcel: 138244020

Review Status: Completed

Review Details: COMMERCIAL - NEW

Permit Number - T16CM09367
Review Name: COMMERCIAL - NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/03/2017 DAVID RIVERA ZONING REVIEW Reqs Change FROM: David Rivera
PDSD Zoning Review Section

PROJECT: T16CM09367 - Shell Building
Building Plan Review (1st Review)
1765 W. Valencia Road - Related to DP16-0183

TRANSMITTAL DATE: January 3, 2017

DUE DATE: January 20, 2017

COMMENTS:

1. COMMENT: Zoning has reviewed the building plans but cannot approve them at this time. While the building plans are consistent with the approved DP zoning cannot approve the Shell building plans until the Commercial Plans Reviewers have reviewed and approved or that the review comments will not require changes to the DP.


2. COMMENT: Zoning will review the building plans on the next submittal as it relates to the zoning review purview and compare the building plan footprint, building height, and square footage to ensure consistency with the approved DP.


If you have any questions about this transmittal, please Steve Shields, (520) 837-4956 or Steve.Shields@tucsonaz.gov
01/12/2017 PIMA COUNTY BUILDING-COMMERCIAL REVIEW Reqs Change T16CM09367 - PLAN REVIEW COMMENTS
Reviewer: Chris Anderson, January 12, 2017
BUILDING – COMMERCIAL
On sheet TS-1, add a scale to the reference site plan and show all utility runs from utility taps to building. Indicate location and size of water meter on site plan.
On sheet TS-1, add keynote legend for the reference site plan.
On sheet TS-1, change the Outdoor Lighting Code edition to 2012 in the Applicable Codes table.
On sheet A1.0, in the U-Factors descriptions, add R-5 continuous insulation for EIFS system at all exterior walls. Ref. IECC Table C402.2. Revise specification if necessary to comply.
On sheet A1.0, in the U-Factors descriptions, add “opaque swing door U-factor to be a maximum of 0.61.” Ref. IECC Table C402.2.
On sheet S1.0, footing sizes on foundation plan and footing schedule do not match what is shown in the structural calculations. Coordinate.
Two columns shown along west wall are not included in structural calculations. Coordinate.
On sheet S2.0, joist J-2 on the Joist Schedule shows 20 gauge joists, however the structural calculations show that J-2 joists should be 18 gauge. Coordinate.
On sheet S2.0, add “SW2” to west end of south wall per structural calculations.
Provide structural calculations for suspended steel awnings.
01/12/2017 PIMA COUNTY PLUMBING-COMMERCIAL REVIEW Approved
01/12/2017 PIMA COUNTY ELECTRICAL-COMMERCIAL REVIEW Approved
01/12/2017 FRODRIG2 WATER REVIEW Approved PER CHRIS AT PIMA COUNTY.
01/12/2017 PIMA COUNTY MECHANICAL-COMMERCIAL REVIEW Reqs Change MECHANICAL – COMMERCIAL
On sheet M2.0, the Rooftop Unit Schedule show that 21 tons of air conditioning will be provided for this 3,100 SF building using 150 SF per ton of air conditioning. Submit basis for this formula.
01/17/2017 FRODRIG2 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
01/17/2017 GERRY KOZIOL WWM REVIEW Reqs Change The following is needed for Sewer Connection Fee Application Approval:



Need PCRWRD/IWC/Steven Valencia review of 500 gallon grease interceptor – 520-724-6200 (steven.valencia@pima.gov)



Need to review the location of building connection to the private sewer (possibly exiting wrong side)





*Fees will be calculated on the basis of a 1-1/2” water meter - $27,30.00 – per plumbing drawings



Hope this helps,

Gerry
12/28/2016 KEN BROUILLETTE FIRE REVIEW Approved
12/29/2016 PAUL BAUGHMAN ENGINEERING REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
01/19/2017 KROBLES1 OUT TO CUSTOMER Completed