Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL - TI ALL
Permit Number - T16CM09359
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/12/2017 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. SHEET T1.2; BUILDING CODE ANALYSIS (REQUIRED PLUMBING FIXTURES): PER THE IBC TABLE 2902.1, WHEN THERE ARE MORE THAN 15 OCCUPANTS, A RESTROOM IS REQUIRED FOR EACH SEX. THIS CAN BE TWO UNISEX RESTROOMS, OR SEPARATE MALE/FEMALE RESTROOMS. PLEASE REVISE THE ANALYSIS AND ALL PERTINENT PLANS. 2. SHEET T1.2 (BUILDING CODE ANALYSIS); SHEET T2.1 (EGRESS PLAN): THE EGRESS PLAN INDICATES 28,132 SF AND 57 OCCUPANTS, WHILE THE BUILDING CODE ANALYSIS INDICATES 18,988 SF AND 38 OCCUPANTS. PLEASE COORDINATE. THIS IS A TENANT IMPROVEMENT FOR ONE PORTION OF THE BUILDING ONLY AND SHOULD NOT INCLUDE THE ENTIRE BUILDING AREA. 3. SHEET T2.1; EGRESS PLAN: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. PLEASE REVISE THE TRAVEL DISTANCES. 4. SHEET T2.1 (EGRESS PLAN); SHEET A1.2 (SITE PLAN); SHEET A2.1 (PLAN): PLEASE VERIFY THE NORTH ARROW ORIENTATIONS ARE COORDINATED ON THESE PLANS. 5. SHEET A2.1; FLOOR PLAN: PLEASE INDICATE THE WALL TYPES AT THE RESTROOM ON THIS PLAN. 6. SHEET A2.1; FLOOR PLAN: PLEASE INDICATE THE DRINKING FOUNTAIN ON THE PLAN. THE DRINKING FOUNTAIN SHALL BE A HIGH/LOW FOUNTAIN, OR A SINGLE POINT OF USE WATER DISPENSER (NO DRAIN REQUIRED). PLEASE REVISE THE ELECTRONIC WATER COOLER (EDF-1 ON SHEET P0.2) TO MEET THE REQUIREMENTS OF THE IBC SECTION 1109.5. 7. SHEET A2.1; FLOOR PLAN: PLEASE VERIFY THE BUILDING ELEVATION INDICATORS MATCH THE BUILDING ELEVATIONS ON SHEET A4.2. ALL INDICATORS REFERENCE SHEET A3.1. 8. SHEET A2.1; FLOOR PLAN AND KEY PLAN: THE KEY PLAN INDICATES THE AREA OF WORK EXTENDS INTO THE AREA ON THE FLOOR PLAN REFERENCED AS 'NOT IN CONTRACT' (NIC). PLEASE CLARIFY. 9. SHEET A2.1 (FLOOR PLAN); NOTES: NOTES 1, 2, AND 4 DO NOT APPEAR ON THE PLAN. PLEASE VERIFY. 10. SHEET A4.2; ELEVATIONS: PLEASE VERIFY THE ELEVATION TITLES INDICATE THE CORRECT DIRECTION AND THE CORRECT ELEVATION NUMBERS. 11. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |
| 01/13/2017 | ROBERT SHERRY | WATER | REVIEW | Reqs Change | Show the location of the reduced pressure backflow assembly on the drawings; indicate the size of the assembly. Reference: Chapter XXVII, Article V, Section 27-72, the Tucson Code, http://www.tucsonaz.gov/files/water/docs/backflow-ordinance.pdf. |
| 01/13/2017 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Coordinate the water heater detail (3/P0.2) with the plumbing fixture schedule and the equipment schedules. Reference: Section 107.2.1, IBC 2012. 2. Provide the number of drinking fountains that complies with the requirements of Section 1109.5.1, IBC 2012 and Section 410.2, IPC 2012. 3. Based on the dimensions of the project area shown on sheet A2.1, the total occupant load of the space is 57, not 38. In either case, two restrooms are required to be installed, one for men and one for women. Reference: Section 2902.2, IBC 2012. 4. Provide a detail to show that the installation of the specified grinder pump assembly complies with the manufacturer's listing requirements (e.g. show the required pipe inverts, the valves, and the minimum drop from the fixtures to the sump). Verify that the proposed vent complies with Table 906.5.1, IPC 2012 for size and maximum length. Reference: Section 303.2, IPC 2012. 5. Provide an automatic faucet for the lavatory, dispensing a maximum of 0.25 gallons per metering cycle. Verify that the automatic faucet will operate for a minimum time of 10-seconds. Reference: Section 416.6, IPC 2012, as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1-09. 6. Provide tempered water for the restroom lavatory using a device conforming to ASSE 1070. Reference: Sections 416.5 and 607.1.2, IPC 2012. 7. Provide an approved vacuum relief valve for the scheduled bottom-fed water heater which is located above the fixture outlets. Reference: Section 504.2, IPC 2012. 8. If the specified water heater is not supplied with integral heat traps, provide heat traps on the supply and discharge piping. Reference: Section C404.4, IECC 2012. 9. If the specified water heater is not supplied with integral heat traps, provide 0.5" of insulation with a maximum conductivity of 0.27 BTU per inch/h F on the first 8 feet of supply and discharge piping. Reference: Section C404.5, IECC 2012. 10. Termination of the excess pressure relief from the water heater over an elevated service sink is not approved location. Reference: Section 504.6 (6), IPC 2012. 11. Revise the water demand calculation using the fixture unit values for public fixtures, not private fixtures. Reference: Sections E102.1 and E103.3 (2.1), IPC 2012. 12. Show the size of the pipe serving the flush valve and verify that it will not result in water velocities greater than that recommended by the pipe manufacturer (e.g. limit the water velocity to less than 8 FPS for copper, PEX, or CPVC piping). At a minimum design flow rate of 25 GPM for a siphonic, flush-valve water closet, a 1" Type L copper pipe has a flow velocity of 9.7 FPS. Reference: Table 604.3, IPC 2012. 13. Show that each trap and trapped fixture has been vented in accordance with one of the methods shown in the IPC. Reference: Section 901.2.1, IPC 2012 |
| 01/17/2017 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Thermostats that are new or are being relocated shall comply with the capabilities required by Section C403.2.4, IECC 2012. Specify the required capabilities for the thermostats. 2. Exhaust fan EF-3 is noted in the outside air calculation on sheet M1.1; where is this fan located? |
| 01/19/2017 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved |