Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T16CM09322
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/14/2016 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 12/14/2016 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Passed | |
| 12/14/2016 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | PLEASE ASSIGN A BRANCH CIRCUIT AND PANEL DESIGNATION FOR THE NEW WALL SCONCES SHOWN ON PLAN SHEET A3 NOTE #7. REF; 2012 IBC 107.2.1, 2011 NEC ART. 408 |
| 12/14/2016 | PAUL BAUGHMAN | ENGINEERING | REVIEW | Approved | |
| 12/14/2016 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | PLEASE PROVIDE STRUCTURAL CALCULATIONS. FURTHER REVIEW WILL BE REQUIRED. |
| 12/14/2016 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 12/14/2016 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
| 12/14/2016 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 12/15/2016 | ARUIZ1 | FIRE | REVIEW | Needs Review |