Review Date Reviewer's Name Type of Review Description Status Comments
12/21/2016 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
12/21/2016 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change The cooling load calculations for suite do not justify the cooling capacities of the two new heat pumps specified for the project. Reference: Sections C403.2.1 and C403.2.2, IECC 2012, and Section 312.1, IMC 2012