Permit Number: T16CM09237
Parcel: 133231390

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T16CM09237
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/09/2016 STEVE SHIELDS ZONING REVIEW Approved
12/09/2016 PAUL BAUGHMAN ENGINEERING REVIEW Approved
12/15/2016 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
12/15/2016 MARTIN BROWN FIRE REVIEW Approved
12/19/2016 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
12/19/2016 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Determine the heating and cooling loads in accordance with the methods shown in ASHRAE Standard 183. Reference: Section C403.2.1, IECC 2012.
2. The HVAC equipment (i.e. the specified packaged heat pumps) shall meet the minimum efficiency requirements. Reference: Section C403.2.3, IMC 2012.
3. Show that each rooftop unit has a thermostatic control that provides for off-hour and set-back control, automatic shutdown and automatic start-up control (i.e. the thermostat is capable of automatically adjusting the start time of the HVAC equipment in order to bring the interior conditions to the desired temperature at the start of occupancy) and, if the thermostat does not require manual changeover from the heating and cooling modes, it restricts set point overlap. Reference: Section C403.2.4, IECC 2012.
12/19/2016 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change T&P relief pipe shall not connect to other pipes.
12/19/2016 ROBERT SHERRY WATER REVIEW Completed
12/19/2016 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
12/21/2016 GERRY KOZIOL WWM REVIEW Completed P16WX02365