Review Date Reviewer's Name Type of Review Description Status Comments
02/09/2017 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. The duct velocities in detail 1/M1.2 indicate segment of the duct with a velocity that is significantly slower than the stated minimum transport velocity of 4500 fpm. Provide calculations to show that the dust collection system has been designed using the constant velocity method. Reference: Section 510.5, IMC 2012.
2. Show how the recirculated air from the dust collector will be monitored to ensure that a failure of the filter cartridges will not result in unacceptable particulate levels in the workspace. Reference: section 510.5.4, IMC 2012.
3. Provide addition information for the spray booth (e.g. listing, dimensions, materials to be used, etc.). Reference: Section 107.2.1, IBC 2012.
02/10/2017 KEN BROUILLETTE FIRE REVIEW Reqs Change Please indicate how compliance with NFPA 664 is being met.

Final Status

Task End Date Reviewer's Name Type of Review Description
02/14/2017 ARUIZ1 OUT TO CUSTOMER Completed