Review Details: REVISION - - 3RD
Permit Number - T16CM09210
Review Name: REVISION - - 3RD
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
02/09/2017 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. The duct velocities in detail 1/M1.2 indicate segment of the duct with a velocity that is significantly slower than the stated minimum transport velocity of 4500 fpm. Provide calculations to show that the dust collection system has been designed using the constant velocity method. Reference: Section 510.5, IMC 2012. 2. Show how the recirculated air from the dust collector will be monitored to ensure that a failure of the filter cartridges will not result in unacceptable particulate levels in the workspace. Reference: section 510.5.4, IMC 2012. 3. Provide addition information for the spray booth (e.g. listing, dimensions, materials to be used, etc.). Reference: Section 107.2.1, IBC 2012. |
02/10/2017 | KEN BROUILLETTE | FIRE | REVIEW | Reqs Change | Please indicate how compliance with NFPA 664 is being met. |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
02/14/2017 | ARUIZ1 | OUT TO CUSTOMER | Completed |