Permit Number: T16CM09111
Parcel: 11502479S

Address:
1611 N 3RD AV

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T16CM09111
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/10/2017 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. SHEET A-0.1; CODE REVIEW: THE APPLICABLE CODE FOR THE COVERED PARKING STRUCTURES IS THE 2012 IBC. PLEASE REVISE THE DRAWING, OR ADD A NEW CODE REVIEW FOR THE NEW PARKING STRUCTURES.
2. SHEET A-0.1; CODE REVIEW: THE OCCUPANCY GROUP FOR THE COVERED PARKING STRUCTURES IS UTILITY (U). PLEASE REVISE THE DRAWING, OR ADD A NEW CODE REVIEW FOR THE NEW PARKING STRUCTURES.
3. SHEET A-0.1; CODE REVIEW: THE CONSTRUCTION TYPE FOR THE COVERED PARKING STRUCTURES IS IIB. PLEASE REVISE THE DRAWING, OR ADD A NEW CODE REVIEW FOR THE NEW PARKING STRUCTURES.
4. SHEET A-0.1; CODE REVIEW: ADD THE SQUARE FOOTAGE OF EACH NEW PARKING STRUCTURE TO THE CODE REVIEW, OR ADD A NEW CODE REVIEW FOR THE NEW PARKING STRUCTURES.
5. SHEET A-0.1; CODE REVIEW: ADD THE ALLOWABLE SQUARE FOOTAGE FOR THE NEW PARKING STRUCTURES PER THE IBC TABLE 503, OR ADD A NEW CODE REVIEW FOR THE NEW PARKING STRUCTURES.
6. SHEET A-0.1 (SITE SECTIONS A-A, B-B, AND C-C); SHEET S1.0 (SECTION A): THE NEW PARKING STRUCTURE SECTIONS ON SHEET A-0.1 INDICATE A CANOPY WIDTH OF 16'-0", WHILE THE SECTION ON SHEET S1.0 INDICATES 17'-0". PLEASE COORDINATE.
7. SHEET S1.0; FRAMING, FOUNDATION, AND LAYOUT PLANS: THESE PLANS INDICATE AN OVERALL LENGTH OF THE NEW PARKING STRUCTURES AS 140'-0". CHANGE THE PLANS TO INDICATE THE ACTUAL LENGTHS OF EACH NEW PARKING STRUCTURE (FOUR STRUCTURES TOTAL).
8. SHEET S1.0 (FRAMING PLAN); STRUCTURAL CALCULATIONS: THE CALCULATIONS INDICATE 2-10" X 2.5" X 14 GA. BEAMS, WHILE THE FRAMING PLAN INDICATES A SINGLE 10' X 2.5" X 14 GA. 'CEE' BEAM. PLEASE COORDINATE.
9. SHEET S1.0 (FOUNDATION PLAN); STRUCTURAL CALCULATIONS: THE CALCULATIONS INDICATE 2-10" X 2.5" X 14 GA. COLUMNS, WHILE THE FOUNDATION PLAN INDICATES A SINGLE 10" X 2.5" X 14 GA. 'CEE' COLUMN. PLEASE COORDINATE.
10. SHEET S1.0; FRAMING PLAN: AN ENLARGED DETAIL 5/S1.1 IS INDICATED ON THE PLAN. THERE IS NO 5/S1.1. PLEASE VERIFY.
11. SHEET S1.1; DETAIL 8: THIS DETAIL INDICATES HOW THE PURLIN CONNECTS TO THE BEAM AT THE END OF THE BEAM. PLEASE ADD A DETAIL INDICATING HOW THE PURLIN CONNECTS TO THE BEAM AT THE MIDDLE OF THE BEAM.
12. SHEET S1.1; DETAIL 1: THE FOOTING NOTE INDICATES 8'-6" L X 4'-0" W X 2'-0" D FOOTING, WHILE THE DIMENSION BELOW THE FOOTING ON THIS DETAIL INDICATES 8'-0". PLEASE COORDINATE (A CALCULATION INDICATES 8'-0" ON A FOOTING SKETCH, BUT 8'-6" IN THE ACTUAL CALCULATION).
13. SHEET S1.1; DETAIL 1: THE COLUMN INDICATES A SINGLE 10" X 2.5" X 14 GA. MEMBER, BUT DETAIL 2 INDICATES 2-10" X 2.5" X 14 GA. MEMBERS. PLEASE COORDINATE.
14. SHEET S1.1; DETAIL 1: THE COLUMN REFERENCES DETAIL 3/S1.1 FOR THE COLUMN DETAIL. PLEASE REVISE THAT REFERENCE TO 2/S1.1.
15. SHEET S1.1; DETAIL 10: THE COLUMN REFERENCES DETAIL 3/S1.1 FOR THE COLUMN DETAIL. PLEASE REVISE THAT REFERENCE TO 2/S1.1.
16. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.

Final Status

Task End Date Reviewer's Name Type of Review Description
01/13/2017 KROBLES1 OUT TO CUSTOMER Completed