Permit Number: T16CM09071
Parcel: 12212043B

Review Status: Completed

Review Details: RESUBMITTAL - TI ALL

Permit Number - T16CM09071
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/13/2017 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Previous comment 10; Sheet S2.1 (Roof framing plan); Sheet S4.0 (Detail 202): The B1 beam as indicated on the plan and beam schedule is still not coordinated with the beam in the detail (note 10). Please coordinate.
2. Previous comment 12; Sheet S2.1: The sheet title is still not revised.
3. Previous comment 14; Sheet S3.0; Detail 104: Note 5 is still not indicated on the detail.
4. Previous comment 15; Sheet S3.0; Detail 105: The embedment of the dowels (notes 3 and 5) are still not indicated.
5. Previous comment 17; Sheet S4.0; Detail 202: Note 13 is still not indicated on the detail.
6. Previous comment 18; Sheet S4.1; Detail 204: Note 4 is still not indicated on the detail.
7. Previous comment 19; Sheet S4.1; Detail 206: Notes 6 and 7 have still not been reversed.
8. Previous comment 20; General: Written responses to all review comments were not provided.
04/18/2017 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
04/19/2017 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Revise the calculations for RTU-2, RTU-5, and RTU-6 using the instructions for multi-zone units. In all cases, the outdoor intake airflow rate should be calculated using equation 4-8, IMC 2012. (In addition, the Zp for Office 17 is 0.04, not 0.12) [Initial comment: Recheck the ventilation calculation for RTU-2. Based on your calculations, Vou/Ev = Vot should be 497 CFM, not 329 CFM. Reference, Section 403.3.2.3.4, IMC 2012.]
2. Comment not addressed; the "infill" walls are new construction and the maximum U-value per table C402.1.2, IECC 2012 is 0.48 BTU/hour per square foot per degree Fahrenheit. [Initial comment: Provide the documentation noted on the Envelope Compliance Certificate (footnote a) for the 'other' components used. Note that new exterior wall sections and fenestration are required to comply with the current energy code. Reference: Section C101.4.3, IECC 2012.]
3. Revise the specifications for the storefront and glass door assemblies to have the same or lower U-values and SHGC values as used in COMcheck. All of the assemblies are to be NFRC-certified. [Initial comment: Provide storefront and vertical fenestration with NFRC-certified U-factor and SHGC values that comply with the requirements of Sections C303.1.3, C402.3, C402.3.3, and C402.3.3.1, IECC 2012.]