Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T16CM09034
Parcel: 123071480

Address:
1225 N WILSON AV

Review Status: Active

Review Details: RESIDENTIAL - BLDG/ZONING-WALKTHRU

Permit Number - T16CM09034
Review Name: RESIDENTIAL - BLDG/ZONING-WALKTHRU
Review Status: Active
Review Date Reviewer's Name Type of Review Description Status Comments
12/02/2016 ANDREW CONNOR ZONING REVIEW Reqs Change COMMENTS: the following comments are relative to an application for a Design Development Option (DDO) (UDC 3.11.1).


This site is located in the R-1 zone (UDC 4.7.8). A single-family residence (SFR) is a permitted use in this zone (Table 4.8-2). See Use-Specific Standards 4.9.7.B.5 - 9.

The minimum setback is the greater of six (6) feet, or two-thirds (2/3) the height of the structure's wall facing each interior property line (Table 6.3-2.A).

Based on a wall height of 12' 5" the required perimeter yard setback to the North property line is 8'.25", proposed perimeter yard is 1'.

Based on a wall height of 11'.1" the required perimeter yard setback to the West property line is 7'.32"", proposed perimeter yard is 4'.6".

Based on a wall height of 12' the required perimeter yard setback to the South property line is 7'.92", proposed perimeter yard is 4'.49".
12/02/2016 ANY ENGINEERING REVIEW Active
12/02/2016 ANDREW CONNOR NPPO REVIEW Passed
12/02/2016 ANY BUILDING-RESIDENTIAL REVIEW Active