Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T16CM09005
Parcel: 115160410

Address:
935 W GRANT RD

Review Status: Completed

Review Details: PLANS OK TO SUBMIT - COMM

Permit Number - T16CM09005
Review Name: PLANS OK TO SUBMIT - COMM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/02/2016 LMAKUS1 ZONING REVIEW Approved
12/02/2016 ENEWCOM1 ADA REVIEW Passed
12/02/2016 KEN BROUILLETTE FIRE REVIEW Approved
12/02/2016 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
12/02/2016 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
12/02/2016 LOREN MAKUS ENGINEERING REVIEW Approved
12/12/2016 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved