333 E WETMORE RD

Review Status: Completed

Review Details: CELL TOWER/ANTENNAS

Permit Number - T16CM08995
Review Name: CELL TOWER/ANTENNAS
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/01/2016 TCRAVEN1 PLANNING-CITY HALL REVIEW Approved
12/15/2016 ROBERT SHERRY BUILDING-COMMERCIAL REVIEW Completed
12/21/2016 FRODRIG2 COMMUNICATIONS REVIEW Approved LETTER SENT TO RECORDS
12/21/2016 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comment. Also provide a written response.
#1. Ref: plan sheet E-1.(one-line dia.). The new 200 amp fuses at the service equipment do not correlate with the existing 100 amp service disconnecting means and the feeder conductor sizes for ampacity rating.
#2. Ref: Cover Plan . Sheet index shows electrical plan sheets E-1 and E-2. Could not locate E-2.

Final Status

Task End Date Reviewer's Name Type of Review Description
01/06/2017 KROBLES1 OUT TO CUSTOMER Completed