Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL - TI ALL
Permit Number - T16CM08878
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
12/07/2016 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. #1. 5 sections ofTrack Lighting and 6 recessed luminaires were added since the last approved plan review ( 8-27-16 ). Please provide revised compliance certificate for the 2012 IECC |
12/07/2016 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | Coordinate the ducts and diffusers locations shown on the HVAC plan. Coordinate also with the reflected ceiling plan (A2) and the lighting plan (E1). Reference: Section 107.2.1, IBC 2012. |