Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T16CM08878
Parcel: 138244040

Review Status: Completed

Review Details: RESUBMITTAL - TI ALL

Permit Number - T16CM08878
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/07/2016 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
#1. 5 sections ofTrack Lighting and 6 recessed luminaires were added since the last approved plan review ( 8-27-16 ). Please provide revised compliance certificate for the 2012 IECC
12/07/2016 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Coordinate the ducts and diffusers locations shown on the HVAC plan. Coordinate also with the reflected ceiling plan (A2) and the lighting plan (E1). Reference: Section 107.2.1, IBC 2012.