Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
12/05/2016 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
12/05/2016 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed | |
12/05/2016 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please provide complete compliance with the 2012 IECC for the interior lighting as requested per the last electrical plan review. Please provide a written response. |
12/05/2016 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | The existing HVAC system was installed for a retail occupancy. The new occupancy is for a barber shop which has different ventilation requirements, including 0.5 CFM/SF general exhaust for the barber area. Show how the mechanical system is to be revised and rebalanced. |