Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T16CM08878
Parcel: 138244040

Review Status: Completed

Review Details: RESUBMITTAL - TI ALL

Permit Number - T16CM08878
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/05/2016 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
12/05/2016 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
12/05/2016 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please provide complete compliance with the 2012 IECC for the interior lighting as requested per the last electrical plan review. Please provide a written response.
12/05/2016 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change The existing HVAC system was installed for a retail occupancy. The new occupancy is for a barber shop which has different ventilation requirements, including 0.5 CFM/SF general exhaust for the barber area. Show how the mechanical system is to be revised and rebalanced.