Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T16CM08868
Parcel: 12701004C

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T16CM08868
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/28/2016 STEVE SHIELDS ZONING REVIEW Approved
11/28/2016 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Clarify how the supply air for each AC unit is able return to the unit without using the egress corridor as a duct.
11/28/2016 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments.
#1. Locate the new 30 KVA transformer 'A' and panel '2ACP' on the electrical floor plans.
#2. The OCPD for transformer 'A' Primary on the one line does not correlate with the panel schedule for 'HDL2'.
#3. The panel schedule for '2ACP' shows this panel as NEW. The one line shows it as existing.
Ref: 2012 IBC 107.2.1, 2011 NEC
11/28/2016 LOREN MAKUS ENGINEERING REVIEW Approved
11/28/2016 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. SHEET A1; FLOOR PLAN/WALL TYPES/KEYED NOTES: PLEASE COORDINATE THE PLAN WITH THE KEYED NOTES AND WALL TYPES LEGEND. IT IS NOT CLEAR WHICH WALLS ON THE PLAN MATCH WHICH WALL TYPES (LEGEND) AND KEYED NOTES.
2. SHEET A1; FLOOR PLAN: IT IS NOT CLEAR WHICH WALL TYPES ARE USED AT THE CONFERENCE ROOM AND NEW RESTROOMS. PLEASE CLARIFY.
3. SHEET A1; FLOOR PLAN: KEYED NOTE 8 INDICATES 34" TALL MILLWORK, WHILE ELEVATION 7/A3 (SEE FINISH FLOOR PLAN ON A2 FOR LOCATION) AND DETAIL 7/A5 BOTH INDICATE 36" TALL. PLEASE CLARIFY.
11/28/2016 ROBERT SHERRY WATER REVIEW Reqs Change Provide the size of the water meter and the reduced pressure backflow preventor along with the total demand served by the meter.
11/28/2016 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Clarify which mixing valve is to be used for the restroom lavatories- the specified (obsolete) model or the model noted in the detail.
11/28/2016 MARTIN BROWN FIRE REVIEW Approved
11/28/2016 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed

Final Status

Task End Date Reviewer's Name Type of Review Description
12/01/2016 LBOJORQ1 APPROVAL SHELF Completed
12/01/2016 LBOJORQ1 OUT TO CUSTOMER Completed
12/01/2016 LBOJORQ1 REJECT SHELF Completed