Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T16CM08868
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/28/2016 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 11/28/2016 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | Clarify how the supply air for each AC unit is able return to the unit without using the egress corridor as a duct. |
| 11/28/2016 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. #1. Locate the new 30 KVA transformer 'A' and panel '2ACP' on the electrical floor plans. #2. The OCPD for transformer 'A' Primary on the one line does not correlate with the panel schedule for 'HDL2'. #3. The panel schedule for '2ACP' shows this panel as NEW. The one line shows it as existing. Ref: 2012 IBC 107.2.1, 2011 NEC |
| 11/28/2016 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | |
| 11/28/2016 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. SHEET A1; FLOOR PLAN/WALL TYPES/KEYED NOTES: PLEASE COORDINATE THE PLAN WITH THE KEYED NOTES AND WALL TYPES LEGEND. IT IS NOT CLEAR WHICH WALLS ON THE PLAN MATCH WHICH WALL TYPES (LEGEND) AND KEYED NOTES. 2. SHEET A1; FLOOR PLAN: IT IS NOT CLEAR WHICH WALL TYPES ARE USED AT THE CONFERENCE ROOM AND NEW RESTROOMS. PLEASE CLARIFY. 3. SHEET A1; FLOOR PLAN: KEYED NOTE 8 INDICATES 34" TALL MILLWORK, WHILE ELEVATION 7/A3 (SEE FINISH FLOOR PLAN ON A2 FOR LOCATION) AND DETAIL 7/A5 BOTH INDICATE 36" TALL. PLEASE CLARIFY. |
| 11/28/2016 | ROBERT SHERRY | WATER | REVIEW | Reqs Change | Provide the size of the water meter and the reduced pressure backflow preventor along with the total demand served by the meter. |
| 11/28/2016 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | Clarify which mixing valve is to be used for the restroom lavatories- the specified (obsolete) model or the model noted in the detail. |
| 11/28/2016 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 11/28/2016 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 12/01/2016 | LBOJORQ1 | APPROVAL SHELF | Completed |
| 12/01/2016 | LBOJORQ1 | OUT TO CUSTOMER | Completed |
| 12/01/2016 | LBOJORQ1 | REJECT SHELF | Completed |