Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T16CM08835
Parcel: 11304148A

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T16CM08835
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/29/2016 MARTIN BROWN FIRE REVIEW Approved
12/16/2016 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. The 2012 International Plumbing Code has been adopted by the City of Tucson. The use of the 2012 Uniform Plumbing Code is allowed (not the 2009 UPC) provided an appeal to the building official is filed. There is no charge for this appeal.
2. Provide corrosion protection for the water pipe penetrating the concrete floor. Reference: Section 305.1, IPC 2012.
3. Provide a cleanout at the junction of the building drain and the building sewer. Show how the horizontal drain within the building will be provided with a cleanout. If the building sewer is to be extended to the existing HCS, provide cleanouts spaced no further apart than 100-feet. Reference: Section 708.3, IPC 2012.
4. Clarify the venting method being used for the two floor sinks. Reference: Section 901.2.1, IPC 2012.
5. The minimum opening dimension for a roof scupper is 4". Reference: Section 1108.3, IPC 2012.
6. Provide overflow protection for the roof. Reference: Sections 1101.7, 1108.1, and 1108.2, IPC 2012, and Sections 1611.1 and 1611.3, IBC 2012.
12/16/2016 ROBERT SHERRY WATER REVIEW Reqs Change Reduced pressure backflow prevention assemblies are required to be installed in locations accessible to Tucson Water. Reference: Chapter XXVII, Article V, Section 27-72, the Tucson Code, http://www.tucsonaz.gov/files/water/docs/backflow-ordinance.pdf
12/16/2016 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
12/27/2016 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please provide full compliance with the Tucson/Pima County Outdoor Lighting Code, for exterior lighting. Can be down loaded from, www.tucsonaz.gov/pdsd.
12/29/2016 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved