Permit Number: T16CM08766
Parcel: 10603008B

Address:
132 E PRINCE RD

Review Status: Completed

Review Details: WALK THRU - COMM

Permit Number - T16CM08766
Review Name: WALK THRU - COMM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/02/2017 ENEWCOM1 FIRE REVIEW Needs Review
03/02/2017 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Needs Review
03/02/2017 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Provide heating/cooling load calculations for the two new rooftop AC units.
2. Specify the programmable thermostats to be installed.
3. Provide calculations to show that adequate ventilation is being supplied to the areas.
03/02/2017 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Show how the gas piping system is to be revised to support the new loads from the new AC units.
2. Provide specifications for the new plumbing fixtures.
03/02/2017 ERIC NEWCOMB ELECTRICAL-COMMERCIAL REVIEW Needs Review