Review Date Reviewer's Name Type of Review Description Status Comments
11/23/2016 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comment. Also provide a written response.
The feeder conduit and conductor sizes for the service disconnect to the wireway do not correlate between the note #4 and the one line diagram, Plan sheet E-01.