Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T16CM08732
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/29/2016 | ANDREW CONNOR | ZONING | REVIEW | Approved | |
| 11/29/2016 | PAUL BAUGHMAN | ENGINEERING | REVIEW | Approved | |
| 11/30/2016 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 11/30/2016 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Confim that there is 18" of clearance from the hood to combustible structure above the hood. 2, Provide 5' of clearance from the property line to the vertical discharge of the new grease exhaust fan. 3. Show that there is sufficient outside air being provided to the building (minimum of 570 CFM from the rooftop units). |
| 11/30/2016 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Clarify the revisions and additions to the existing grease waste and sanitary drains (i.e. provide a riser diagram). 2. Provide cleanouts sized per the size of the pipes served. |
| 11/30/2016 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 11/30/2016 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 12/08/2016 | KROBLES1 | BUILDING-COMMERCIAL | REVIEW | Needs Review | |
| 12/08/2016 | KROBLES1 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review | |
| 12/08/2016 | KROBLES1 | WWM | REVIEW | Needs Review |