Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T16CM08732
Parcel: 12801033A

Address:
6211 E 22ND ST

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T16CM08732
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/29/2016 ANDREW CONNOR ZONING REVIEW Approved
11/29/2016 PAUL BAUGHMAN ENGINEERING REVIEW Approved
11/30/2016 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
11/30/2016 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Confim that there is 18" of clearance from the hood to combustible structure above the hood.
2, Provide 5' of clearance from the property line to the vertical discharge of the new grease exhaust fan.
3. Show that there is sufficient outside air being provided to the building (minimum of 570 CFM from the rooftop units).
11/30/2016 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Clarify the revisions and additions to the existing grease waste and sanitary drains (i.e. provide a riser diagram).
2. Provide cleanouts sized per the size of the pipes served.
11/30/2016 MARTIN BROWN FIRE REVIEW Approved
11/30/2016 ROBERT SHERRY WATER REVIEW Completed
12/08/2016 KROBLES1 BUILDING-COMMERCIAL REVIEW Needs Review
12/08/2016 KROBLES1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review
12/08/2016 KROBLES1 WWM REVIEW Needs Review