Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T16CM08716
Parcel: 136290020

Review Status: Completed

Review Details: CELL TOWER/ANTENNAS

Permit Number - T16CM08716
Review Name: CELL TOWER/ANTENNAS
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/28/2016 MARTIN BROWN FIRE REVIEW Reqs Change Please provide manufacturer's cut sheets on the diesel tanks and generators, showing UL and/or FM listings.
11/28/2016 LOREN MAKUS ENGINEERING REVIEW Passed
12/01/2016 STEVE SHIELDS ZONING REVIEW Reqs Change PDSD TRANSMITTAL

FROM: Steve Shields
Principal Planner

PROJECT: 3951 S. Pantano Rd. - Generator Replacement
T16CM08716
Cell Site Plan (1st Review)

TRANSMITTAL DATE: December 1, 2016

1. The Cell site plans have been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed.

2. The plans only reference "EXISTING VERIZON WIRELESS 48KW GENERATOR ON EXISTING SLAB", is this not a new generator replacing the existing.

3. Zoning cannot approve the plans until stamped and approved by the PDSD Special Exception Section.

4. Until the above comments have been addressed and all other PDSD review agencies have approved the building plans zoning cannot approve.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956
12/05/2016 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. SHEET E-1; SITE PLAN 1: A NOTE ON THIS PLAN INDICATES AN EXISTING GENERATOR INSIDE THE EQUIPMENT SHELTER. SHOULD THIS BE THE NEW GENERATOR? PLEASE VERIFY.
2. SHEET E-1: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. PLEASE REVISE.
3. SHEET E-1: PLEASE INCLUDE A DETAIL FOR THE CONNECTION OF THE NEW GENERATOR TO THE EXISTING EQUIPMENT SHELTER SLAB.
4. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
12/22/2016 ARUIZ1 COMMUNICATIONS REVIEW Completed
12/22/2016 ARUIZ1 ELECTRICAL-COMMERCIAL REVIEW Needs Review
12/22/2016 ARUIZ1 PLANNING-CITY HALL REVIEW Completed

Final Status

Task End Date Reviewer's Name Type of Review Description
12/22/2016 ARUIZ1 OUT TO CUSTOMER Completed