Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T16CM08709
Parcel: 11803348C

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/WWM

Permit Number - T16CM08709
Review Name: RESIDENTIAL - BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/06/2016 LOREN MAKUS ENGINEERING REVIEW Reqs Change Grading permit (DP) with Hillside Development review required before approval.
12/14/2016 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Reqs Change T16CM08709
PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, please provide two sets of updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2012 International Residential Code and 2012 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

GENERAL COMMENTS:

1. All SFR and Duplex plans submitted after March 1, 2009 require a solar water system, or future installation preparation City of Tucson Ordinance #10549 with one of the following provisions: ½"control conduit and two ¾" copper piping for water with rooftop termination; straight 3" capped sleeve; or an accessible attic (clear path 30" wide x 30" high) over the water heater. Show appropriate notation.

FLOOR PLANS:

1. Show a maximum ½" floor elevation change at a notated accessible route entrance on the floor plan, R106.1.1.

PLUMBING PLANS:

1. Provide devices rated for application, G2406.3. A two-way valve is not appropriate for building drainage, and is not required for a future tap point for collection..

MECHANICAL PLANS:

1. Provide (an HVAC system with) whole-house mechanical ventilation with continuous or a minimum controlled intermittent airflow rate, R303.4 & M1507.3. Show a source of outside supply air or continuous exhaust fan function.

OUTDOOR LIGHTING CODE

1. Adjustable security light fixtures are unshielded, not FCO; see OLC 3.1.2. Update the description on fixture type C.
If you have any questions please contact:
Ken Van Karsen
(520) 837-4912
City of Tucson Residential Plan Review

Final Status

Task End Date Reviewer's Name Type of Review Description
01/03/2017 LBOJORQ1 OUT TO CUSTOMER Completed