Review Date Reviewer's Name Type of Review Description Status Comments
11/18/2016 ANDREW CONNOR ZONING REVIEW Approved
11/18/2016 PAUL BAUGHMAN ENGINEERING REVIEW Approved
11/23/2016 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
11/23/2016 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. SHEET A2.0; FLOOR PLAN: AT THE NORTH WALL OF THE THEATER, AN 'A' SYMBOL IS INDICATED. WHAT DOES THIS REFERENCE?
2. SHEET A2.0; FLOOR PLAN KEYNOTE 15: THIS NOTE INDICATES A NEW GLU-LAM BEAM PER DETAILS 1, 2, AND 3 ON SHEET A2.1. PLEASE INDICATE THE BEAM AND FOOTINGS ON SHEET A2.0.
3. SHEET A2.1; DETAIL 2: PLEASE INDICATE ON THE DETAIL HOW THE NEW FOUNDATION WILL TIE INTO THE EXISTING WALL FOOTINGS AND SLAB.
4. SHEET A2.1; DETAIL 4: PLEASE INDICATE ON THE DETAIL HOW THE NEW FOOTING WILL TIE INTO THE EXISTING WALL FOOTINGS AND SLAB.
5. SHEET A3.0; REFLECTED CEILING PLAN: SECTIONS 5 AND 8 ON SHEET A6.0 ARE CUT AT THE WEST THEATER WALL. PLEASE INDICATE HOW THOSE TWO DETAILS ARE CONNECTED TO EACH OTHER.
6. GENERAL: PLEASE PROVIDE A STRUCTURAL PLAN INDICATING NEW COLUMNS, BEAMS, AND FOUNDATIONS. SHEET A2.0 DOES NOT CLEARLY DEPICT STRUCTURAL REVISIONS AND ADDITIONS.
7. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
11/23/2016 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
11/28/2016 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
11/28/2016 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
11/28/2016 MARTIN BROWN FIRE REVIEW Approved
11/28/2016 ROBERT SHERRY WATER REVIEW Completed