Permit Review Detail
Review Status: Completed
Review Details: CELL TOWER/ANTENNAS
Permit Number - T16CM08671
Review Name: CELL TOWER/ANTENNAS
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/05/2016 | MARTIN BROWN | FIRE | REVIEW | Reqs Change | Please provide manufacturer's cut sheets on the diesel tanks and generators, showing UL and/or FM listings. |
| 12/05/2016 | LOREN MAKUS | ENGINEERING | REVIEW | Passed | |
| 12/05/2016 | STEVE SHIELDS | ZONING | REVIEW | Reqs Change | PDSD TRANSMITTAL FROM: Steve Shields Principal Planner PROJECT: 6680 S. Country Club Rd - Generator Replacement T16CM08671 Cell Site Plan (1st Review) TRANSMITTAL DATE: December 1, 2016 1. The Cell site plans have been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed. 2. The plans only reference "EXISTING VERIZON WIRELESS 48KW GENERATOR ON EXISTING SLAB", is this not a new generator replacing the existing. 3. Zoning cannot approve the plans until stamped and approved by the PDSD Special Exception Section. 4. Until the above comments have been addressed and all other PDSD review agencies have approved the building plans zoning cannot approve. If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956 |
| 12/07/2016 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. SHEET E-1; SITE PLAN 1: A NOTE ON THIS PLAN INDICATES AN EXISTING GENERATOR INSIDE THE EQUIPMENT SHELTER. SHOULD THIS BE THE NEW GENERATOR? PLEASE VERIFY. 2. SHEET E-1: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. PLEASE REVISE. 3. SHEET E-1: PLEASE INCLUDE A DETAIL FOR THE CONNECTION OF THE NEW GENERATOR TO THE EXISTING EQUIPMENT SHELTER SLAB. 4. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |
| 12/22/2016 | ARUIZ1 | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 12/22/2016 | ARUIZ1 | OUT TO CUSTOMER | Completed |