Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T16CM08663
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/18/2016 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 12/09/2016 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. SHEET G101; CODE ANALYSIS (PLUMBING FIXTURES): THE IBC TABLE 2902.1 REQUIRES ONE DRINKING FOUNTAIN (HIGH/LOW OR SINGLE POINT OF USE), AND ONE SERVICE SINK FOR A 'B' OCCUPANCY WITH THE OCCUPANT LOAD OF MORE THAN 15. PLEASE REVISE THE TABLE ON SHEET G101 AND ADD THESE FIXTURES TO THE FLOOR PLAN. 2. SHEET G101; CODE ANALYSIS (OCCUPANCY CLASSIFICATION): A NOTE ON THE BUILDING OCCUPANCY INDICATES 'MIXED USE NON-SEPARATED PER 302.3.1'. THERE IS NO SECTION 302.3.1 IN THE 2012 IBC. MIXED USE IS DISCUSSED IN SECTION 508 (NONSEPARATED OCCUPANCY IN SECTION 508.3). PLEASE REVISE THE DRAWING. 3. SHEET A104; PARTITION TYPES: THE PARTITION TYPE TAG WAS NOT LOCATED ON THE FLOOR PLAN (SHEET A101). PLEASE INDICATE THOSE TAGS AND REFERENCE SHEET A104 FOR PARTITION TYPES. 4. SHEET A104; PARTITION TYPES 3 AND 4: AT THE SECTION VIEW, PLEASE INDICATE THE DIAGONAL BRACE (AT TOP OF WALL) SPACING AND THE NUMBER AND SIZE OF CONNECTORS USED AT THE WALL CONNECTION. IN ADDITION, PROVIDE A DETAIL (OR DETAILS) OF HOW THE DIAGONAL BRACE CONNECTS TO THE STRUCTURE ABOVE (INCLUDE NUMBER AND SIZE OF CONNECTORS). 5. SHEET A105; RESTROOM ELEVATIONS 19(B): PER THE ICC/ANSI FIGURE 604.5.1, THE DISTANCE FROM THE FLOOR TO THE BOTTOM OF THE VERTICAL GRAB BAR IS 39" TO 41". PLEASE REVISE ON THE ELEVATION B. 6. SHEET A201; COUNTER ELEVATION 05: PLEASE INDICATE THE ACCESSIBLE PORTION OF THE COUNTER IS A MINIMUM OF 36" IN LENGTH AND 36" MAXIMUM IN HEIGHT PER THE ICC/ANSI SECTION 904.3.1 FOR PARALLEL APPROACH. 7. SHEET A201: PLEASE INDICATE THESE INTERIOR ELEVATIONS ON THE FLOOR PLAN. 8. GENERAL: PLEASE ADD A PLAN AND DETAIL TO THE DRAWINGS PER THE ICC/ANSI FIGURE 602.5 FOR THE ACCESSIBLE DRINKING FOUNTAIN. 9. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |
| 12/09/2016 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 12/09/2016 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Revise the font size used on the drawings to a minimum of 3/32-inch. Reference: Section 107.2.1, IBC 2012 2. Provide the minimum plumbing facilities required by Table 2902.1, IBC 2012, for business occupancy (e.g. a drinking fountain). Reference: Sections 1109.5 and 2902.1, IBC 2012. 3. Provide structural calculations and installation details for the mounting shelf for the water heater to show that the water heater will be safely supported from the building structure. Reference: Section 301.2, IPC 2012. 4. Provide further description and the listing information for the "generic fixture." Reference: Sections 303.4 and 402, IPC 2012 and Section 107.2.1, IBC 2012. 5. Provide automatic faucets for the restroom lavatories, dispensing a maximum of 0.25 gallons per metering cycle. Verify that the automatic faucets will operate for a minimum time of 10-seconds. Reference: Section 416.6, IPC 2012, as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1-09. 6. Provide tempered water for the restroom lavatories using approved devices conforming to ASSE 1070. Reference: Sections 416.5 and 607.1.2, IPC 2012. 7. Provide cleanouts sized for the nominal size of pipes that they serve up to 4-inches (i.e. provide a 3" cleanout for the 3" horizontal drain running east though room 12). Reference: Section 708.7, IPC 2012. |
| 12/09/2016 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Show the size, routing, and termination of the condensate drains (not found on the plumbing drawings). Reference: Section 307.2.1, IMC 2012 as amended by the City of Tucson. 2. Verify that the specified HVAC systems are provided with controls that are capable of automatically adjusting the start time of the HVAC equipment in order to bring the interior conditions to the desired temperature at the start of occupancy. Reference: Section C403.2.4.3.3, IECC 2012. 3. Verify that the materials used in the construction of the building shell and the proposed tenant improvement are listed for use in the return air plenum. Reference: Section 602.2.1, IMC 2012. 4. Show how a path for the return air will be provided in rooms 101 and 119. Reference: section 107.2.1, IBC 2012. |
| 12/15/2016 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comment. Also provide a written response. Please designate a branch circuit and panel for the FIRE ALARM CONTROL PANEL shown on plan sheet FA100. Also reflect this on the panel schedule. Ref:2012 IBC 107.2.1, 2011 NEC 408. |