Review Date Reviewer's Name Type of Review Description Status Comments
01/11/2017 PIMA COUNTY BUILDING-COMMERCIAL REVIEW Approved
01/11/2017 PIMA COUNTY MECHANICAL-COMMERCIAL REVIEW Reqs Change MECHANICAL – COMMERCIAL
In regards to response to previous mechanical comment 1, “the engineer calculations indicate a 12 ton design load” is incorrect. Per the submitted cooling load calculations, 3.3 tons (AC-1) + 3.0 tons (AC-2) + 2.7 tons (AC-3) = 9 tons required cooling. If you intend to reuse the existing unit for AC-1 (5 tons) and reuse the existing unit for AC-3 (4 tons) as you show on the revised plan, the existing equipment supply the required cooling per the load calculations without addition of a new 3-ton AC-2. Adding an additional 3 tons puts this development out of compliance with IECC C403.2.2.
01/11/2017 PIMA COUNTY PLUMBING-COMMERCIAL REVIEW Reqs Change T16CM08564 - PLAN REVIEW COMMENTS #2
Reviewer: Christopher Anderson, January 11, 2017
PLUMBING – COMMERCIAL
In regards to response to previous plumbing comment 3, show a service sink on the plumbing plan instead of a floor sink, show hot and cold water to service sink on plan, add service sink to the plumbing fixture schedule and delete FS-1, change “FLOOR SINK” in the Fixture Unit Count table to “SERVICE SINK,” and revise the plumbing isometric to show a service sink.
01/12/2017 FRODRIG2 WWM REVIEW Approved
01/12/2017 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed