Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T16CM08574
Review Name: RESUBMITTAL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
01/11/2017 | PIMA COUNTY | BUILDING-COMMERCIAL | REVIEW | Approved | |
01/11/2017 | PIMA COUNTY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | MECHANICAL – COMMERCIAL In regards to response to previous mechanical comment 1, “the engineer calculations indicate a 12 ton design load” is incorrect. Per the submitted cooling load calculations, 3.3 tons (AC-1) + 3.0 tons (AC-2) + 2.7 tons (AC-3) = 9 tons required cooling. If you intend to reuse the existing unit for AC-1 (5 tons) and reuse the existing unit for AC-3 (4 tons) as you show on the revised plan, the existing equipment supply the required cooling per the load calculations without addition of a new 3-ton AC-2. Adding an additional 3 tons puts this development out of compliance with IECC C403.2.2. |
01/11/2017 | PIMA COUNTY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | T16CM08564 - PLAN REVIEW COMMENTS #2 Reviewer: Christopher Anderson, January 11, 2017 PLUMBING – COMMERCIAL In regards to response to previous plumbing comment 3, show a service sink on the plumbing plan instead of a floor sink, show hot and cold water to service sink on plan, add service sink to the plumbing fixture schedule and delete FS-1, change “FLOOR SINK” in the Fixture Unit Count table to “SERVICE SINK,” and revise the plumbing isometric to show a service sink. |
01/12/2017 | FRODRIG2 | WWM | REVIEW | Approved | |
01/12/2017 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed |