Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T16CM08530
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/10/2016 | ANDREW CONNOR | ZONING | REVIEW | Approved | |
| 11/10/2016 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Provide COMcheck envelope compliance certificate for the building addition. Verify that the storefront is NFRC certified. 2. Revise the ventilation calculations to include the supply air flow rates to each room and change the zone air distribution efficiency (Ez) to 0.8. 3. Revise the control sequence for the restroom fan so that all of the air supplied to the restroom is exhausted. |
| 11/10/2016 | KEN VAN KARSEN | ELECTRICAL-COMMERCIAL | REVIEW | Completed | |
| 11/10/2016 | PAUL BAUGHMAN | ENGINEERING | REVIEW | Approved | |
| 11/10/2016 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 11/10/2016 | ROBERT SHERRY | WATER | REVIEW | Reqs Change | Verify the size of the existing water meter and provide its serial number. |
| 11/10/2016 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Provide a temperature mixing valve listed to ASSE 1070 for the lavatory sink. 2. Verify the developed length of the hot water supply. If it is greater than 50-feet, provide a recirculating hot water system. |
| 11/10/2016 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 11/10/2016 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed |