Permit Number: T16CM08530
Parcel: 113074130

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T16CM08530
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/10/2016 ANDREW CONNOR ZONING REVIEW Approved
11/10/2016 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Provide COMcheck envelope compliance certificate for the building addition. Verify that the storefront is NFRC certified.
2. Revise the ventilation calculations to include the supply air flow rates to each room and change the zone air distribution efficiency (Ez) to 0.8.
3. Revise the control sequence for the restroom fan so that all of the air supplied to the restroom is exhausted.
11/10/2016 KEN VAN KARSEN ELECTRICAL-COMMERCIAL REVIEW Completed
11/10/2016 PAUL BAUGHMAN ENGINEERING REVIEW Approved
11/10/2016 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
11/10/2016 ROBERT SHERRY WATER REVIEW Reqs Change Verify the size of the existing water meter and provide its serial number.
11/10/2016 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Provide a temperature mixing valve listed to ASSE 1070 for the lavatory sink.
2. Verify the developed length of the hot water supply. If it is greater than 50-feet, provide a recirculating hot water system.
11/10/2016 MARTIN BROWN FIRE REVIEW Approved
11/10/2016 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed