Permit Number: T16CM08401
Parcel: 10820051H

Address:
4036 N 1ST AV

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T16CM08401
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/20/2016 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
12/20/2016 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Riser 1 now shows both an ASSE 1024 double check valve and an ASSE 1013 RPBP: which device will be installed? [Initial comment: Clarify the type of double check valve assembly that is specified for water connections 1, 2, and 5 (i.e. ASSE Standard number). Reference: Sections 608.1 and 608.3, IPC 2012.]
2. The plumbing plan (P1.1) and detail PSD-7A show the compartment drains combined. [Initial comment: Provide separate indirect waste pipes for each compartment of the 3-compartment sink to protect against cross-contamination or fouling. Reference: Sections 801.2 and 802.1.8, IPC 2012.]