Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T16CM08401
Parcel: 10820051H

Address:
4036 N 1ST AV

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T16CM08401
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/23/2016 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
11/30/2016 ROBERT SHERRY WATER REVIEW Completed
11/30/2016 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Clarify the type of double check valve assembly that is specified for water connections 1, 2, and 5 (i.e. ASSE Standard number). Reference: Sections 608.1 and 608.3, IPC 2012.
2. Provide separate indirect waste pipes for each compartment of the 3-compartment sink to protect against cross-contamination or fouling. Reference: Sections 801.2 and 802.1.8, IPC 2012.
3. Clarify the plan views in detail PSD-7A. It appears that they show directly-connected drains for the 3-compartment sink. Reference: Sections 801.2 and 802.1.8, IPC 2012.
4. The trap for the new floor sink located by the new 12' service meat case is located approximately 10-feet from its vent (waste and vent riser "B"). Reference: Section 909.1, IPC 2012.
5. Where does the single-compartment sink detail, PSD-5A, occur? Reference: section 107.2.1, IBC 2012.
11/30/2016 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Revise the font size used on the drawings to a minimum of 3/32-inch (refrigeration sheets). Reference: Section 107.2.1, IBC 2012.
12/07/2016 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved