Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T16CM08401
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
11/23/2016 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
11/30/2016 | ROBERT SHERRY | WATER | REVIEW | Completed | |
11/30/2016 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Clarify the type of double check valve assembly that is specified for water connections 1, 2, and 5 (i.e. ASSE Standard number). Reference: Sections 608.1 and 608.3, IPC 2012. 2. Provide separate indirect waste pipes for each compartment of the 3-compartment sink to protect against cross-contamination or fouling. Reference: Sections 801.2 and 802.1.8, IPC 2012. 3. Clarify the plan views in detail PSD-7A. It appears that they show directly-connected drains for the 3-compartment sink. Reference: Sections 801.2 and 802.1.8, IPC 2012. 4. The trap for the new floor sink located by the new 12' service meat case is located approximately 10-feet from its vent (waste and vent riser "B"). Reference: Section 909.1, IPC 2012. 5. Where does the single-compartment sink detail, PSD-5A, occur? Reference: section 107.2.1, IBC 2012. |
11/30/2016 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | Revise the font size used on the drawings to a minimum of 3/32-inch (refrigeration sheets). Reference: Section 107.2.1, IBC 2012. |
12/07/2016 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved |