Permit Number: T16CM08391
Parcel: 103090670

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T16CM08391
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/07/2016 PAUL BAUGHMAN ENGINEERING REVIEW Approved
11/08/2016 MARTIN BROWN FIRE REVIEW Approved
11/18/2016 PIMA COUNTY BUILDING-COMMERCIAL REVIEW Reqs Change Reviewer: Chris Anderson
BUILDING – COMMERCIAL
On sheet A2.0, Door Hardware Schedule, suite entry doors “A” must comply with IBC 1008.19. “Egress doors shall be readily openable from the egress side without the use of a key or special knowledge.”
On sheet A3.0, cabinetry configurations in break rooms 117.03, 155.02 and 169.03 do not comply with ICC/ANSI A117.1 sections 606.2 (exception 1) and 804.5.6. For parallel wheelchair approach to appliances and sinks, the appliance must be centered on the 30” x 48” required clear floor space (section 305).
11/18/2016 PIMA COUNTY MECHANICAL-COMMERCIAL REVIEW Approved
11/18/2016 PIMA COUNTY ELECTRICAL-COMMERCIAL REVIEW Reqs Change ELECTRICAL – COMMERCIAL
Provide an indoor wattage calculation per IECC C405.5.2.
On sheet E2.0, Lighting Plan, move exit light above north exist doors to a location visible from the south end of the hall.
On sheet E3.0, Power Plan, and Panel “A” Schedule and Load Calculation on sheet E4.0, add electric water heater for coffee area 177.03.
11/18/2016 FRODRIG2 WATER REVIEW Approved PER CHRIS ANDERSON AT PIMA COUNTY
11/18/2016 PIMA COUNTY PLUMBING-COMMERCIAL REVIEW Reqs Change PLUMBING – COMMERCIAL
Is there an existing mop/service sink in this building? If yes, show it on plumbing plan on sheet P1.0 and plumbing fixture schedule on sheet P2.0. I not, provide new as required by IBC Table 2902.1.
On sheet P2.0, Plumbing Schedule, change “Demo” Fixtures above P-1 to “(N)” Fixtures.
11/21/2016 GERRY KOZIOL WWM REVIEW Approved
11/29/2016 DAVID RIVERA ZONING REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
12/13/2016 LBOJORQ1 APPROVAL SHELF Completed
12/13/2016 LBOJORQ1 OUT TO CUSTOMER Completed
12/13/2016 LBOJORQ1 REJECT SHELF Completed