Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T16CM08390
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/07/2016 | PAUL BAUGHMAN | ENGINEERING | REVIEW | Approved | |
| 11/08/2016 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 11/18/2016 | PIMA COUNTY | BUILDING-COMMERCIAL | REVIEW | Reqs Change | Reviewer: Chris Anderson BUILDING – COMMERCIAL On sheet A2.0, Door Hardware Schedule, suite entry doors “A” must comply with IBC 1008.19. “Egress doors shall be readily openable from the egress side without the use of a key or special knowledge.” On sheet A3.0, cabinetry configurations in break rooms 117.03, 155.02 and 169.03 do not comply with ICC/ANSI A117.1 sections 606.2 (exception 1) and 804.5.6. For parallel wheelchair approach to appliances and sinks, the appliance must be centered on the 30” x 48” required clear floor space (section 305). |
| 11/18/2016 | PIMA COUNTY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 11/18/2016 | PIMA COUNTY | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | ELECTRICAL – COMMERCIAL Provide an indoor wattage calculation per IECC C405.5.2. On sheet E2.0, Lighting Plan, move exit light above north exist doors to a location visible from the south end of the hall. On sheet E3.0, Power Plan, and Panel “A” Schedule and Load Calculation on sheet E4.0, add electric water heater for coffee area 177.03. |
| 11/18/2016 | FRODRIG2 | WATER | REVIEW | Approved | PER PIMA COUNTY - CHRIS ANDERSON |
| 11/18/2016 | PIMA COUNTY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | PLUMBING – COMMERCIAL Is there an existing mop/service sink in this building? If yes, show it on plumbing plan on sheet P1.0 and plumbing fixture schedule on sheet P2.0. I not, provide new as required by IBC Table 2902.1. On sheet P2.0, Plumbing Schedule, change “Demo” Fixtures above P-1 to “(N)” Fixtures. |
| 11/21/2016 | GERRY KOZIOL | WWM | REVIEW | Approved | |
| 11/29/2016 | DAVID RIVERA | ZONING | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 12/13/2016 | LBOJORQ1 | APPROVAL SHELF | Completed |
| 12/13/2016 | LBOJORQ1 | OUT TO CUSTOMER | Completed |
| 12/13/2016 | LBOJORQ1 | REJECT SHELF | Completed |