Permit Review Detail
Review Status: Active
Review Details: COMMERCIAL - TI
Permit Number - T16CM08374
Review Name: COMMERCIAL - TI
Review Status: Active
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/04/2016 | ANDREW CONNOR | ZONING | REVIEW | Approved | |
| 11/04/2016 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | Clarify the nature of the exhaust from the lab. Positively pressurized exhaust ducts from areas allowed to have up to 10% recirculation per Section 403.2.1 item 4, may not pass through a plenum unless the duct is sealed in accordance with Section 603.9, IMC 2012. Reference: Section 601.4, IMC 2012. |
| 11/04/2016 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 11/04/2016 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | |
| 11/04/2016 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 11/04/2016 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 11/04/2016 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Needs Review | |
| 11/04/2016 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 11/07/2016 | KEN BROUILLETTE | FIRE | REVIEW | Reqs Change | need items listed by mechanical to be completed prior to fire approval |
| 11/17/2016 | FRODRIG2 | WWM | REVIEW | Approved | PER GERRY KOZIOL AT PIMA COUNTY WASTEWATER. |