Permit Number: T16CM08374
Parcel: 11621302C

Review Status: Active

Review Details: COMMERCIAL - TI

Permit Number - T16CM08374
Review Name: COMMERCIAL - TI
Review Status: Active
Review Date Reviewer's Name Type of Review Description Status Comments
11/04/2016 ANDREW CONNOR ZONING REVIEW Approved
11/04/2016 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Clarify the nature of the exhaust from the lab. Positively pressurized exhaust ducts from areas allowed to have up to 10% recirculation per Section 403.2.1 item 4, may not pass through a plenum unless the duct is sealed in accordance with Section 603.9, IMC 2012. Reference: Section 601.4, IMC 2012.
11/04/2016 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
11/04/2016 LOREN MAKUS ENGINEERING REVIEW Approved
11/04/2016 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
11/04/2016 ROBERT SHERRY WATER REVIEW Completed
11/04/2016 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Needs Review
11/04/2016 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
11/07/2016 KEN BROUILLETTE FIRE REVIEW Reqs Change need items listed by mechanical to be completed prior to fire approval
11/17/2016 FRODRIG2 WWM REVIEW Approved PER GERRY KOZIOL AT PIMA COUNTY WASTEWATER.