Permit Number: T16CM08234
Parcel: 117131560

Address:
192 S STONE AV

Review Status: Completed

Review Details: WALK THRU - COMM

Permit Number - T16CM08234
Review Name: WALK THRU - COMM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/31/2016 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please verify sizes and capacity for the feeder replacement of the Cathedral existing SES. The feeders per keynote #10, ( 3 sets 500 MCM ) are sized for 1140 amps ( cu ) per NEC table 310.15 B(16)-75C, and the load calcs show 1991 amps.