Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: WALK THRU - COMM
Permit Number - T16CM08234
Review Name: WALK THRU - COMM
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
10/31/2016 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please verify sizes and capacity for the feeder replacement of the Cathedral existing SES. The feeders per keynote #10, ( 3 sets 500 MCM ) are sized for 1140 amps ( cu ) per NEC table 310.15 B(16)-75C, and the load calcs show 1991 amps. |