Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Permit Number - T16CM08209
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/01/2016 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 11/17/2016 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | OUTDOOR LIGHTING COMMENT Please address the following electrical plan review comment. The Tucson / Pima County Outdoor Lighting Code can be downloaded from www.tucsonaz.gov/pdsd. #1. Provide all the information in detail as outlined and or required in sections 104.2, 104.2.1, thru 106 and other sections or that may apply to your project. Include this information in the plan documents (Lighting Plans) for approval. Also be advised, lamp color temperature cannot exceed 3500 kelvin per sec. 402.1. #2. Indicate the conduit, conductor sizes and types and wiring methods utilized to intercept the existing branch circuit conductors for the new pole lighting. Ref: IBC 107.2.1, 2011 NEC, Tucson / Pima County Outdoor Lighting Code. |
| 11/29/2016 | CLAYTON TREVILLYAN | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Provide structural calculations for new footings identified on sheet E-1 2. Identify pole height above proposed footing 3. Specify depth of proposed footing |
| 11/30/2016 | CTREVIL1 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 01/24/2017 | ARUIZ1 | OUT TO CUSTOMER | Completed |