Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T16CM08114
Parcel: 135074550

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T16CM08114
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/26/2016 ANDREW CONNOR ZONING REVIEW Approved
10/26/2016 PAUL BAUGHMAN ENGINEERING REVIEW Approved
10/26/2016 MARTIN BROWN FIRE REVIEW Approved
11/09/2016 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
11/09/2016 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
11/09/2016 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. SHEET A2; FLOOR PLAN: PER THE IBC SECTION 1108.2.9.1, ACCESSIBLE SEATING IS REQUIRED IN THE DINING/DRINKING AREA. PLEASE INDICATE ON THE PLAN THE NUMBER OF REQUIRED ACCESSIBLE SEATS, AND INDICATE THOSE SEATS ON THE PLAN.
2. SHEET A2; DETAILS 1 AND 2: PLEASE DARKEN THE LETTERING.
3. SHEET A2; FLOOR PLAN: ALL DETAIL CUTS REFERENCE SHEET A3. PLEASE REVISE.
4. SHEET A2; FLOOR PLAN: PLEASE CUT DETAIL 2 ON THE PLAN.
5. SHEET A4; HANDICAP STANDARDS: PLEASE DARKEN THE DIMENSIONS.
11/09/2016 ROBERT SHERRY WATER REVIEW Completed
11/09/2016 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. The hot water outlet at the 3-compartment sink in the tasting room is over 50-feet from the water heater; revise the design to comply with Section 607.2, IPC 2012.
2. Show that the relocated lavatories are supplied with tempered water and metering faucets.
11/09/2016 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed