Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - NEW
Permit Number - T16CM07978
Review Name: COMMERCIAL - NEW
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
10/24/2016 | MARTIN BROWN | FIRE | REVIEW | Approved | |
10/31/2016 | STEVE SHIELDS | ZONING | REVIEW | Reqs Change | PDSD TRANSMITTAL FROM: Steve Shields Principle Planner PROJECT: T16CM07978 Building Plan (1st Review) TRANSMITTAL DATE: October 31, 2016 1. The building plans have been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed. 2. Until the above comments have been addressed and all other PDSD review agencies have approved the building plans zoning cannot approve. If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956 |
11/04/2016 | PIMA COUNTY | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | ELECTRIC - COMMERCIAL Add directional exit sign to Lighting Floor Plan 1/E100 in dining area and pointing to exit @ restrooms. |
11/04/2016 | PIMA COUNTY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | PLUMBING - COMMERCIAL Per City of Tucson amendment to the 2012 IPC Section 1003.3, all floor sinks and floor drains in the kitchen/food processing area shall be connected to the grease interceptor. Connect floor sink located at ice maker to grease interceptor drain line. On Plumbing Fixture Schedule confirm that lavatory faucet HS-1B complies with City of Tucson amendment to the 2012 IPC, new Section 424.10. Lavatory faucets shall be automatic and dispensing no more than 0.25 gallon per metering cycle. |
11/04/2016 | PIMA COUNTY | BUILDING-COMMERCIAL | REVIEW | Reqs Change | T16CM07978 - PLAN REVIEW COMMENTS Reviewer: Christopher Anderson, November 3, 2016 BUILDING – COMMERCIAL On sheet A014, add note “A. U-factor for exterior insulated steel doors shall be maximum 0.064 (R-15.625)” to Section 08110 (2). This will comply with the building envelope COMcheck. On sheet A015, change U-factor for aluminum storefront, Section 084113 (1.4)(B)(5), to 0.38. Add to this note “storefront entrance doors to have maximum U-factor of 0.60.” This will bring specification in compliance with submitted building envelope COMcheck. Detail 11/A102 indicates a 7’-6” tall masonry dumpster enclosure wall. Submit structural calculations sealed by an Arizona registrant. Detail 11/A102 does not match what is shown on the architectural site plan. Site plan shows two, staggered, 12’ x 14’ enclosures. Provide structural calculations (static, lateral and overturning loading) for building sealed by an Arizona registrant to justify the proposed structural design shown on sheets S000 – S202. Provide structural calculations and details for the steel canopy over the entrance doors as shown on wall section 1/A302. PLEASE PROVIDE SITE UTILITY PLAN. |
11/04/2016 | PAUL BAUGHMAN | ENGINEERING | REVIEW | Reqs Change | PDSD Engineering can not approve this plan until an updated development package is approved and any changes to drainage documented in an updated drainage report. Please note that an updated drainage report is requested to accompany the revision to DP16-0044 to reflect the changes in layout proposed by this plan. |
11/04/2016 | PIMA COUNTY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | MECHANICAL - COMMERCIAL Submit heating and cooling calculations with summary sheets for each specified unit to justify capacities of selected equipment. Per C403.2.2 the output capacities of heating and cooling equipment and systems shall not exceed the loads calculated in accordance with C403.2.1. The Rooftop Unit Schedule on sheet M200 appears to indicate that peak design air temperature for cooling is 109 degrees F. However, the Tucson summer design air temperature is 104-degrees F per City of Tucson amendment to the 2012 IECC, new Tables C302.1. Provide outside air calculations. Indicate how exhaust fans EF-2 and EF-3 will comply with IMC Table 403.3, including notes e and g. Verify that the specified HVAC systems are provided with controls that are capable of automatically adjusting the start time of the HVAC equipment in order to bring the interior conditions to the desired temperature at the start of occupancy per IECC C403.2.4.3.3. |
11/04/2016 | FRODRIG2 | WATER | REVIEW | Reqs Change | WATER – COMMERCIAL PER CHRISTOPHER ANDERSON Provide water calculations. |
11/08/2016 | FRODRIG2 | WWM | REVIEW | Reqs Change | PCRWRD Connection Fee review comments: Need addressing review – may be using administration address for this project Need PDEQ/Construction Authorization for the private sewer and a COT/Private Sewer Permit approval Need copy of private sewer for map guide update Need public manhole permit for connection private sewer to the existing public sewer – PCRWRD Sylvia Quinlan 724-6649 Needs PCRWRD/IWC/Steve Valencia review of 1500 gallon grease interceptor – 724-6200 Need to clarify the size of the new water meter to be utilized for Chipolte and the size, serial number and location of any water meters(with User Fee History) removed for wastewater credit evaluation (if applicable) Kurt Stemm has issued a Type III capacity approval per permit #P16WC00279 dated 11/4/16 |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
12/16/2016 | LBOJORQ1 | OUT TO CUSTOMER | Completed |