Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Permit Number - T16CM07950
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/04/2017 | PIBARRA1 | ENGINEERING | REVIEW | Approved | |
| 10/21/2016 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. #1. The lighting calc's and location should be per lighting area E3 not E2. #2. Indicate on the plans whether a special inspection is required per sec. 106.2 Tucson/Pima County Outdoor Lighting Code (OLC). #3. Type CVC conduit is not an approved raceway per NEC. #4. The luminaire schedule shows both types of luminaires as type 'A'. #5. Indicate conduit, conductor sizes and types on the site plan. #6. Designate circuit numbers, panel and luminaire type for all the luminaires at their locations on the site plan. #7. Provide load calc's and AIC rating on the panel schedule. Ref: 2012 IBC sec 107.2.1, 2011 NEC, CITY OF TUCSON COMMERCIAL PLAN SUBMITTAL REQUIREMENTS (ELECTRICAL), TUCSON/PIMA COUNTY OUTDOOR LIGHTING CODE. |
| 10/21/2016 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | PLEASE PROVIDE STRUCTURAL CALCULATIONS FOR THE LIGHT POLE FOUNDATION. |
| 10/21/2016 | ANDREW CONNOR | ZONING | REVIEW | Approved | |
| 10/24/2016 | MARTIN BROWN | FIRE | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 01/04/2017 | PIBARRA1 | OUT TO CUSTOMER | Approved |