Review Date Reviewer's Name Type of Review Description Status Comments
07/20/2017 STEVE SHIELDS ZONING REVIEW Reqs Change P&DS TRANSMITTAL


FROM: Steve Shields,
Principle Planner

PROJECT:
T17CM07935
548 S. Via Golondrina
Enclose carport to garage and add exercise room, workshop and porch

TRANSMITTAL: July 20, 2017

COMMENTS: the following comments are relative to an application for a Design Development Option (DDO) (UDC 3.11.1).

This site is located in the RX-1 zone (UDC 4.7.6). A single-family residence (SFR) is a permitted use in this zone (Table 4.8-3). See Use-Specific Standards 4.9.7.B.5 - 9.

The minimum setback is twenty feet (20) facing each interior property line (Table 6.3-1.A).

The proposed perimeter yard setbacks from the proposed;
Garage to the north property line is 10'-0".
Work shop to the north property line is 11'-0".
Proposed porch, supporting column, to the north property line is 16'-0".

A DDO will need to be approved prior to approval of the residential building plan.