Review Details: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Permit Number - T16CM07935
Review Name: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/20/2017 | STEVE SHIELDS | ZONING | REVIEW | Reqs Change | P&DS TRANSMITTAL FROM: Steve Shields, Principle Planner PROJECT: T17CM07935 548 S. Via Golondrina Enclose carport to garage and add exercise room, workshop and porch TRANSMITTAL: July 20, 2017 COMMENTS: the following comments are relative to an application for a Design Development Option (DDO) (UDC 3.11.1). This site is located in the RX-1 zone (UDC 4.7.6). A single-family residence (SFR) is a permitted use in this zone (Table 4.8-3). See Use-Specific Standards 4.9.7.B.5 - 9. The minimum setback is twenty feet (20) facing each interior property line (Table 6.3-1.A). The proposed perimeter yard setbacks from the proposed; Garage to the north property line is 10'-0". Work shop to the north property line is 11'-0". Proposed porch, supporting column, to the north property line is 16'-0". A DDO will need to be approved prior to approval of the residential building plan. |