Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T16CM07902
Review Name: RESUBMITTAL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
11/14/2016 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. The employee restroom opens directly into the room that contains the prep sink. [Initial comment: Per Section 403.3.2, IPC 2012, toilet rooms shall not open directly into a room used to prepare food for public service.] 2. Comment not resolved; see sheet P1 and coordinate the fixture labels shown in the waste isometric on sheet P4 (the water isometric is correct). [Initial comment: Relabel the urinal on the waste isometric (i.e. it should be P-3, not P-4). Reference: section 107.2.1, IBC 2012.] 3. The specifications refer to the thickness and conductivity of the insulation to be used both above and underground but do not state what type of insulation is to be used underground (a wet location). [Initial comment: Specify the insulation to be used for the underground hot water piping. Reference: Section C404.5, IEEC 2012.] |
11/14/2016 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | Previous comments not addressed. |