Permit Number: T16CM07902
Parcel: 137055380

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T16CM07902
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/14/2016 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. The employee restroom opens directly into the room that contains the prep sink. [Initial comment: Per Section 403.3.2, IPC 2012, toilet rooms shall not open directly into a room used to prepare food for public service.]
2. Comment not resolved; see sheet P1 and coordinate the fixture labels shown in the waste isometric on sheet P4 (the water isometric is correct). [Initial comment: Relabel the urinal on the waste isometric (i.e. it should be P-3, not P-4). Reference: section 107.2.1, IBC 2012.]
3. The specifications refer to the thickness and conductivity of the insulation to be used both above and underground but do not state what type of insulation is to be used underground (a wet location). [Initial comment: Specify the insulation to be used for the underground hot water piping. Reference: Section C404.5, IEEC 2012.]
11/14/2016 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Previous comments not addressed.