Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T16CM07767
Parcel: 122151990

Address:
3308 E GRANT RD

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T16CM07767
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/14/2016 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
11/14/2016 ROBERT SHERRY WATER REVIEW Completed
11/14/2016 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed