Permit Number: T16CM07767
Parcel: 122151990

Address:
3308 E GRANT RD

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T16CM07767
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/12/2016 PAUL BAUGHMAN ENGINEERING REVIEW Approved
10/13/2016 STEVE SHIELDS ZONING REVIEW Approved
10/13/2016 MARTIN BROWN FIRE REVIEW Approved
11/08/2016 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
11/08/2016 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Revise the sequence of operation for EF-1 and EF-2 so that they operate whenever HVAC air is supplied to the rooms.
2. Provide an envelope and mechanical COMcheck ealuation of the modifications to the building.
11/08/2016 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
11/08/2016 ROBERT SHERRY WATER REVIEW Reqs Change The projected demand is in excess of the maximum flow rate for a 5/8" water meter.
11/08/2016 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Provide scupper calculations.
2. Provide overflow capacity for the west wing roof that discharges to a visible and separate location than the primary roof drain.
3. Provide a service sink and a drinking fountain.
11/08/2016 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed