Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T16CM07767
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/12/2016 | PAUL BAUGHMAN | ENGINEERING | REVIEW | Approved | |
| 10/13/2016 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 10/13/2016 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 11/08/2016 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 11/08/2016 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Revise the sequence of operation for EF-1 and EF-2 so that they operate whenever HVAC air is supplied to the rooms. 2. Provide an envelope and mechanical COMcheck ealuation of the modifications to the building. |
| 11/08/2016 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 11/08/2016 | ROBERT SHERRY | WATER | REVIEW | Reqs Change | The projected demand is in excess of the maximum flow rate for a 5/8" water meter. |
| 11/08/2016 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Provide scupper calculations. 2. Provide overflow capacity for the west wing roof that discharges to a visible and separate location than the primary roof drain. 3. Provide a service sink and a drinking fountain. |
| 11/08/2016 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed |