Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T16CM07743
Parcel: 10820051K

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T16CM07743
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/11/2016 STEVE SHIELDS ZONING REVIEW Approved
10/11/2016 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Verify the capacity of the existing rooftop heat pump; the shell drawings indicate the that a 7.5-ton unit was to be installed for this suite. Reference: section 107.2.1, IBC 2012.
2. Show the size, routing, and termination of the condensate drain for the rooftop heat pump. Reference: Section 307.2.1, IMC 2012 as amended by the City of Tucson.
3. Revise the sequence of operation for the restroom exhaust fan so that all of the air supplied to the restrooms will be exhausted (i.e. all of the air supplied to each restroom is to be exhausted during the hours of operation even if the lights are off). Reference: Section 403.2.1 (4), IMC 2012.
4. Show the size, route, and termination of the dryer exhaust duct. Reference: Sections 504.1, 504.2, 504.4 and, 504.6, IMC 2012.
10/11/2016 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
10/11/2016 PAUL BAUGHMAN ENGINEERING REVIEW Approved
10/11/2016 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. SHEET INDEX: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. PLEASE REVISE.
2. SHEET B1.0: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. PLEASE REVISE.
3. SHEET B1.0; ACCESSIBLE CODE: THIS PROJECT WILL BE REVIEWED UNDER THE 2009 ICC/ANSI A117.1 ACCESSIBILITY CODE (PER THE CODE INFORMATION INDICATED ON THE INDEX SHEET). PLEASE REMOVE ALL ADAAG AND 2010 ACCESSIBILITY CODE REFERENCES.
4. SHEET B1.0; GRAB BARS: PLEASE INDICATE THE VERTICAL GRAB BAR AT ALL RESTROOM ELEVATIONS PER THE ICC/ANSI FIGURE 604.5.1.
5. SHEET A1: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. PLEASE REVISE DETAIL 3..
6. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
10/11/2016 ROBERT SHERRY WATER REVIEW Completed
10/11/2016 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Provide an automatic faucet for the lavatory, dispensing a maximum of 0.25 gallons per metering cycle. Verify that the automatic faucet will operate for a minimum time of 10-seconds. Reference: Section 416.6, IPC 2012, as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1-03.
2. Provide an approved vacuum relief valve for the scheduled bottom-fed water heater which is located above the fixture outlets. Reference: Section 504.2, IPC 2012.
3. Provide separate indirect waste pipes for each compartment of the 3-compartment sink to protect against cross-contamination or fouling. Reference: Sections 801.2 and 802.1.8, IPC 2012.
4. Verify that the Pima County Regional Wastewater Reclamation Department will allow the drain from the sanitizing compartment of the 3-compartment sink to bypass the grease interceptor. Reference: Section 1003.3, IPC 2012, as amended by the City of Tucson.
5. Show how (i.e. provide a detail) the flow control device is to be installed below the floor level and in accordance with the manufacturer's instructions. Reference: Section 1003.4.2, IPC 2012.
10/11/2016 KEN BROUILLETTE FIRE REVIEW Approved
10/11/2016 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Approved