Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T16CM07708
Parcel: 13414011A

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T16CM07708
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/07/2017 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comment. Also provide a written response.
The one line diagrams show the inverter output connection at the closest position to the utility power input connection to the service equipment bus. This is a violation of NEC art 705.12D7, 2011 NEC. The interconnection should be at the opposite end from the input feeder location.

Final Status

Task End Date Reviewer's Name Type of Review Description
07/10/2017 MMENDIB1 OUT TO CUSTOMER Completed