Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T16CM07708
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/07/2017 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comment. Also provide a written response. The one line diagrams show the inverter output connection at the closest position to the utility power input connection to the service equipment bus. This is a violation of NEC art 705.12D7, 2011 NEC. The interconnection should be at the opposite end from the input feeder location. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 07/10/2017 | MMENDIB1 | OUT TO CUSTOMER | Completed |