Permit Number: T16CM07698
Parcel: 11615088L

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T16CM07698
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/10/2016 STEVE SHIELDS ZONING REVIEW Approved
10/10/2016 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
10/10/2016 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
10/10/2016 ROBERT SHERRY WATER REVIEW Completed
10/10/2016 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. SHEET g1.0 (CODE INFORMATION); SHEET g1.2 (CODE REVIEW): THE CONSTRUCTION TYPE IS INDICATED AS II-B ON SHEET g1.0 AND I-B ON SHEET g1.2. PLEASE COORDINATE.
2. SHEET g1.2: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. PLEASE REVISE THE DIMENSION ON THE EGRESS FLOOR PLAN.
3. SHEET a1.0: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. PLEASE REVISE THE REFERENCE FLOOR PLAN ROOM IDENTIFICATIONS.
4. SHEET a2.0; KEYNOTES: MANY OF THE NOTES ARE RELEVANT TO THE PLANS ON SHEET a2.1 ONLY. PLEASE REMOVE THOSE NOTES FROM THIS SHEET.
5. SHEETS a2.0 AND a2.1; PLANS: THE MD ROOM EAST OF RESTROOM 1556 IS EDENTIFIED AS 1556. PLEASE VERIFY.
6. SHEET a2.1; KEYNOTES: ON NOTES 10 AND 11, PLEASE INDICATE THE STUD SPACING IN THE NEW WALLS.
7. SHEET a2.1; KEYNOTES: MANY OF THE NOTES ARE RELEVANT TO THE PLANS ON SHEET a2.0 ONLY. PLEASE REMOVE THOSE NOTES FROM THIS SHEET.
8. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
10/10/2016 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
10/10/2016 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
10/11/2016 KEN BROUILLETTE FIRE REVIEW Reqs Change Need the type of construction clarified. See building review comment
10/31/2016 LBOJORQ1 ENGINEERING REVIEW Needs Review