Permit Number - T16CM07690
Review Name: CELL TOWER/ANTENNAS
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/11/2016 | KEN BROUILLETTE | FIRE | REVIEW | Approved | |
| 10/14/2016 | ROBERT SHERRY | BUILDING-COMMERCIAL | REVIEW | Reqs Change | The scope of work for this activity is the replacement of twelve existing antennas with twelve new antennas. The submitted calculations however are for the installation of a new monopole and foundation. Provide calculations that address the capability of the existing monopole and foundation to safely support the new equipment. Reference: Section 107.2.1, IBC 2012. |
| 10/19/2016 | FRODRIG2 | COMMUNICATIONS | REVIEW | Approved | LETTER SENT TO RECORDS |
| 11/04/2016 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved |