Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: CELL TOWER/ANTENNAS
Permit Number - T16CM07690
Review Name: CELL TOWER/ANTENNAS
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
10/11/2016 | KEN BROUILLETTE | FIRE | REVIEW | Approved | |
10/14/2016 | ROBERT SHERRY | BUILDING-COMMERCIAL | REVIEW | Reqs Change | The scope of work for this activity is the replacement of twelve existing antennas with twelve new antennas. The submitted calculations however are for the installation of a new monopole and foundation. Provide calculations that address the capability of the existing monopole and foundation to safely support the new equipment. Reference: Section 107.2.1, IBC 2012. |
10/19/2016 | FRODRIG2 | COMMUNICATIONS | REVIEW | Approved | LETTER SENT TO RECORDS |
11/04/2016 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
02/14/2017 | LBOJORQ1 | OUT TO CUSTOMER | Completed |