Permit Number: T16CM07685
Parcel: 11713039A

Address:
20 E BROADWAY BL

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T16CM07685
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/04/2017 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. The callouts for waste and vent isometrics C/P2.1 and E/P2.1 still appear to be mislabeled (i.e. reversed) on sheet P1.0. [Initial comment: The callouts for waste and vent isometrics C/P2.1 and E/P2.1 appear to be mislabeled on sheet P1.0. In addition, verify the labeling of the showers (P-3) in isometric C/P2.1 and show the installation of the lavatories (P-1) in isometric E/P2.1.]
2. The floor drain is specified as 2" on sheet P3.0. [Initial comment: Revise the size of the floor drain for the central clothes washing facility per Section 412.4, IPC 2012 (the minimum size shall be 3"). The floor drain is not shown on the waste and vent isometric (B).]
3. The 4" inlet hub for the specified ejector pump system is supplied unattached by the manufacturer. Provide guidance to the contractor for the proper location for the inlet hub. (i.e. minimum height above the alarm level). Note: the manufacturer's literature appears to show the check and shut-off valves located within the sump; how will this be modified to comply with the requirements of Section 712.2, IPC 2012. [Initial comment: Provide a detail of the installation of the ejector pump system including the dimensions of the sump, the inlet pipe, and effluent control levels. Verify that the maximum effluent level in the sump is 2" below the invert of the gravity inlet. Reference: Section 712.3.4, IPC 2012.]
4. The plumbing waste floor plans incorrectly show the upper floors discharging through the backwater valve. [Initial comment: The rim elevation of the next upstream sanitary manhole (2387.43') is higher than the first floor elevation (2387.07'). Provide a backwater valve; floors discharging from above the first floor shall not discharge through the backwater valve. Reference: Section 715.1, IPC 2012, as amended by the City of Tucson.]
5. The summation of the roof areas is still incorrect. [Initial comment: Provide a size for each segment of the rainwater and overflow leaders. Correct the summation of the roof areas. Reference: Section 107.2.1, IBC 20012.]
01/06/2017 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
01/06/2017 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
12/16/2016 STEVE SHIELDS ZONING REVIEW Reqs Change FROM: David Rivera for Steve Shields - Principal Planner
PDSD Zoning Review Section

PROJECT: T16CM07685
Building Plans for Multi-Use Residential Tower (1st Review)
10 E Broadway Boulevard - OCR-2 Zone

TRANSMITTAL DATE: December 16, 2016

DUE DATE: January 13, 2017


1. Zoning has reviewed the building plans but cannot approve them at this time.

2. Revisions to the DP and IID application must be approved prior to the next building plan review.

3. Zoning will review the building plans on the next submittal and do a review and comparison of the building plans with the revised DP and IID plans.
12/30/2016 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. PREVIOUS COMMENT 12; SHEET T4.0; ADDED NOTE TO DRAWING: THE NEW NOTE REFERENCES THE IBC SECTION 3029 FOR ALLOWING REMOVAL OF EMERGENCY ESCAPE FROM R-2 OCCUPANCIES BELOW THE FOURTH FLOOR. YOUR RESPONSE INDICATES THE BUILDING OFFICIAL (CLAYTON TREVILLYAN) HAS APPROVED THIS CONDITION AS HAS THE ICC CODE CORRELATION SYSTEM COMMITTEE IN CODE PROPOSAL IBC27-09CCC. THIS ISSUE MUST BE REVIEWED BY THE BUILDING OFFICIAL AND THE PLAN REVIEWER IN THE CITY OF TUCSON. IN ADDITION, IS THE IBC SECTION REFERENCE CORRECT? PLEASE VERIFY.
2. PREVIOUS COMMENTS 32, 33, 34, 35, 36, 37, 38, AND 39: SHEET S2.1 IS MISSING FROM THIS SUBMITTAL SET. PLEASE ADD FOR REVIEW.
3. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.